Case: T07FR00311
Case Details
Entered Date:
02/12/2007
Applicant:
EL DORADO VENTURES LLC
Description:
Complaint Leach07#2484 re: elect room bldg 1
Outstanding Inspections
Case Number: T07FR00311
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 02/21/2007 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Correction Required | TFC 315.2 - Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. _____ Storage shall be orderly and safe. |
| 02/21/2007 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Correction Required | TFC 315.2.3 - Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. _____ Remove storage from electrical room, Building 9. |
| 02/21/2007 | VIOL - FIRE SERVICE FEATURES | DGREENLE | Correction Required | TFC 505.1 - New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. _____ Address shall be displayed in an approved manner. Manager received a copy of the "Pima County Address Display Requirements" flyer. |
| 02/21/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panel in an approved manner. |
| 02/21/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | 605.3.1 - Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. _____ Provide such signage. |
| 02/21/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Rewire light, Building 1, mechanical room. |
| 02/21/2007 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Correction Required | TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____ Fire-rated walls & ceilings shall be intact (poke-throughs). |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00311
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2007 | COMPLIANCE | DGREENLE | Approved | Re-Inspection 3/15/07 - Approved to go on SIP |