Inspection History Details
Inspection Status: Approved
Inspection History: INSP - AST/UST
Case Number - T07FR00295
Inspection Description - INSP - AST/UST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/12/2007 | INSP - AST/UST | Approved | Both ASTs have been removed from the site. | |
02/09/2007 | INSP - AST/UST | Continued | Met with Southwest Hazard and purged the second tank with CO2. Tank passed the test with O2 reading 6.4%. Tank was removed today. | |
02/08/2007 | INSP - AST/UST | Correction Required | Scheduled to purge and remove 2 x 2300 ASTs that are in the parking lot of the TCC. On inspection we found 19" of diesel fuel in one of the tanks. The tank was posted with a field notice with instructions and a red tag. Pictures taken. Jim from SWHazard Control was on site to purge, tank must be pumped out prior to purge. | |
02/08/2007 | INSP - AST/UST | Continued | One tank in compliance and removed. |