Case: T07FR00295

Parcel: 117200250


Addresses:

270 S STONE AV


Inspection Status: Approved

Inspection History: INSP - AST/UST

Case Number - T07FR00295

Inspection Description - INSP - AST/UST

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2007 INSP - AST/UST Approved Both ASTs have been removed from the site.
02/09/2007 INSP - AST/UST Continued Met with Southwest Hazard and purged the second tank with CO2. Tank passed the test with O2 reading 6.4%. Tank was removed today.
02/08/2007 INSP - AST/UST Correction Required Scheduled to purge and remove 2 x 2300 ASTs that are in the parking lot of the TCC. On inspection we found 19" of diesel fuel in one of the tanks. The tank was posted with a field notice with instructions and a red tag. Pictures taken. Jim from SWHazard Control was on site to purge, tank must be pumped out prior to purge.
02/08/2007 INSP - AST/UST Continued One tank in compliance and removed.