Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR00027
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2007 | VIOL - MEANS OF EGRESS | Approved | 1. All bolts/locks removed. 2. All Exit signs repaired. 3. Emergency illumination repaired. |
|
| 01/29/2007 | VIOL - MEANS OF EGRESS | Violation | 1. Main entrance door has panic hardware, plus thumblatch, plus 1/4 turn handle. TFC-1027.6 Panic hardware. When panic and fire exit hardware is installed, whether required or not, panic or exit fire hardware shall be the only locking device on the door except where otherwise permitted in this code. ***remove thumblatch and 1/4 turn handle from main business entrance. |
|
| 01/29/2007 | VIOL - MEANS OF EGRESS | Violation | 2. Exit signs not lit in regular and/or emergency mode. -2nd floor office spaces. (3) -Front office north wing. (2) TFC-1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. ***Repair Exit signs. |
|
| 01/29/2007 | VIOL - MEANS OF EGRESS | Violation | 3. Exit illumination out of service. -2nd floor office space. -Main office, North wall. -Front office, East wall. TFC-1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate area. ***Repair lighting. |