Case: T07FR00027

Parcel: 138241690


Addresses:

6700 S PELLA DR


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00027

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2007 VIOL - MEANS OF EGRESS Approved 1. All bolts/locks removed.
2. All Exit signs repaired.
3. Emergency illumination repaired.
01/29/2007 VIOL - MEANS OF EGRESS Violation 1. Main entrance door has panic hardware, plus thumblatch, plus 1/4 turn handle.
TFC-1027.6 Panic hardware. When panic and fire exit hardware is installed, whether required or not, panic or exit fire hardware shall be the only locking device on the door except where otherwise permitted in this code.
***remove thumblatch and 1/4 turn handle from main business entrance.
01/29/2007 VIOL - MEANS OF EGRESS Violation 2. Exit signs not lit in regular and/or emergency mode.
-2nd floor office spaces. (3)
-Front office north wing. (2)
TFC-1026.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated from
an external source, shall have an intensity of not less than 5
foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.
***Repair Exit signs.
01/29/2007 VIOL - MEANS OF EGRESS Violation 3. Exit illumination out of service.
-2nd floor office space.
-Main office, North wall.
-Front office, East wall.
TFC-1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate area.
***Repair lighting.