| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | 5. Access to FDC's cleared, functional. 6. Approved sign installed to alert incoming crews of FDC location. |
|
| 01/29/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 5. Access to Fire Department Connections blocked by bushes, Zone 4/7. TFC-912.3 Access. Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other object for a minimum of 3 feet (914 mm). ***Clear path to FDC's. |
|
| 01/29/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 6. Visibility of FDC's from street. Zone 4/7 FDC's not readily visible from street. TFC-912.4 Signs. A metal sign with raised letters at least 1 inch (25 mm) in size shall be mounted on all fire department connections serving fire sprinklers. Such signs shall read: FIRE DEPARTMENT CONNECTIONS. ***Install sign directly above water gong and well above shrubbery height as to be seen easily from the street. |