Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL02202
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/24/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
01/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPAIR TO GROUNDING ELECTRODE CONDUCTORS TO ALL THREE SERVICES THAT SUPPLY POWER TO THIS STRUCTURE TO BE DONE BY LICENSED ELECTRICAL CONTRACTOR AND SEPARATE REPAIR PERMIT. REPAIR TO BE MADE PER REQUIREMENTS OF NEC 250.64 C1 CONTRACTOR TO BE ON SITE TO OPEN EQUIPMENT FOR INSPECTION. |
|
12/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSIDE 1. REPLACE ALL CRACKED OR PAINTED OVER DEVICES 2. INSTALL ALL COVER PLATES 3. COMPLETE CORRECTION FROM 12/21/07 |
|
12/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNIT TO BE UNLOCKED FOR INSPECTION 2) GROUNDING ELECTRODE CONDUCTORS FOR ALL THREE SERVICES THAT SUPPLY POWER FOR THIS BLDG HAVE BEEN STOLEN. YOU WILL NEED A LICENSED ELECTRICAL CONTRACTOR TO MAKE THE REPAIRS |