Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE APPROVED RISER BRACE, HOMEMADE OUT OF SMASHED EMT NOT APPROVED. USE LISTED ASSEMBLY 2. USE PERMANENT ADDRESS LABEL FOR SERVICE ADDRESS, MUST BE SCREWED OR RIVETED TO ENCLOSURE 3. USE MIN. 1/4" BOLTS TO SUPPORT RISER CONDUIT TO WALL 4. SHEETMETAL OR WOOD SCREW NOT APPROVED TO GROUND J-BOX USE NUT & BOLT, SCRAP OFF ENAMEL 5. VERIFY WATER BOND |