Permit: T07EL02103

Parcel: 135112210


Addresses:

2201 S MARC DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/08/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/21/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL GROUND RODS MIN 6' APART
2) INSTALL FILLER BLANKS IN DEAD FRONT
3) NEED DETAILED PANEL SCHEDULE
4) NEED PROTECTIVE BUSHING AROUND WIRES THROUGH BACK OF PANEL. SEAL OPENING WITH NON-COMBUSTIBLE MATERIAL
5) SUB PANEL NOT GROUNDED PROPERLY
6) INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT AND ? STRIP
7) ONE NEUTRAL PER TERMINAL NOT TO BE SHARED BY OTHER WIRES