Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/21/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL GROUND RODS MIN 6' APART 2) INSTALL FILLER BLANKS IN DEAD FRONT 3) NEED DETAILED PANEL SCHEDULE 4) NEED PROTECTIVE BUSHING AROUND WIRES THROUGH BACK OF PANEL. SEAL OPENING WITH NON-COMBUSTIBLE MATERIAL 5) SUB PANEL NOT GROUNDED PROPERLY 6) INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT AND ? STRIP 7) ONE NEUTRAL PER TERMINAL NOT TO BE SHARED BY OTHER WIRES |