Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/28/2008 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
2) SEAL OPENING IN BOTTOM OF PANEL
12/04/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED LISTED MAST BRACE - NOT EMT
2. GROUND RODS TO BE MINIMUM 6' APART
3. NEED PROPER TYPE BREAKERS FOR PANEL
4. WELDER BOX & RECEPTACLE TO BE RAIN TIGHT
5. IDENTIFY PANEL DIRECTORY
6. BOND GAS PIPE
7. PROPERLY CONNECT GROUNDS FOR TV & PHONE
8. MAX 15 AMP BREAKER FOR 14GA HOUSE WIRING (OR #12 COPPER) CORRECT AS NEEDED