Permit: T07EL01904

Parcel: 129052940


Addresses:

2837 E EASTLAND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/21/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LISTED MAST BRACING CANNOT USE MINERALLAC STRAP & SMASHED EMT - NEC 110.3 & 230.28
2. REMOVE PAINT AT GROUND CLAMP CONNECTON ON
WATER PIPE - NEC 250.12
3. PROVIDE DETAILED PANEL SCHEDULE WITH NO ABBREVIATIONS - NEC 408.4
4. CONNECT BONDING JUMPER FOR GAS PIPE TO GROUND/NEUTRAL BAR IN PANEL NOT METER SECTION. NEEDS TO BE ACCESSIBLE. NEC 250.104
5. HAS ENTIRE HOUSE BEEN REWIRED? PLEASE REVISE PERMIT FOR WORK DONE INSIDE HOUSE.