Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING CANNOT USE MINERALLAC STRAP & SMASHED EMT - NEC 110.3 & 230.28 2. REMOVE PAINT AT GROUND CLAMP CONNECTON ON WATER PIPE - NEC 250.12 3. PROVIDE DETAILED PANEL SCHEDULE WITH NO ABBREVIATIONS - NEC 408.4 4. CONNECT BONDING JUMPER FOR GAS PIPE TO GROUND/NEUTRAL BAR IN PANEL NOT METER SECTION. NEEDS TO BE ACCESSIBLE. NEC 250.104 5. HAS ENTIRE HOUSE BEEN REWIRED? PLEASE REVISE PERMIT FOR WORK DONE INSIDE HOUSE. |