Permit: T07EL01886

Parcel: 10612016A

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07EL01886

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Denied

Date Description Inspector Results Comments
02/08/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PERMITS STILL NEEDED FOR INTERIOR TRAILER WORK
01/08/2008 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. MOVE RACEWAY FROM IN FRONT OF SERVICE - NEC 110.26
2. NEED TO INSPECT INTERIOR OF UNIT BEFORE POWER RELEASED. GET PERMITS AS REQUIRED FOR ALTERATIONS TO TRAILER
01/04/2008 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
12/04/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PROPER TYPE BREAKER
2. ROMEX NOT ALLOWED UNDERGROUND/THROUGH CONDUIT
3. STRANDED/SOLID GROUND NOT TO BE UNDER SAME SCREW
4. PIPE TO BE ELECTRICAL PVC/NOT PLUMBING
5. IDENTIFY SPACE # AT PEDESTAL
6. A PERMIT IS NEEDED FOR ALL TRAILER REMODEL
7. CONDUIT COVERED BEFORE INSPECTION,
TO BE MINIMUM 18" DEEP
8. NO TRAILER INSPECTION AT THIS TIME.
11/14/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*