Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T07EL01886
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PERMITS STILL NEEDED FOR INTERIOR TRAILER WORK |
|
01/08/2008 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. MOVE RACEWAY FROM IN FRONT OF SERVICE - NEC 110.26 2. NEED TO INSPECT INTERIOR OF UNIT BEFORE POWER RELEASED. GET PERMITS AS REQUIRED FOR ALTERATIONS TO TRAILER |
|
01/04/2008 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
12/04/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PROPER TYPE BREAKER 2. ROMEX NOT ALLOWED UNDERGROUND/THROUGH CONDUIT 3. STRANDED/SOLID GROUND NOT TO BE UNDER SAME SCREW 4. PIPE TO BE ELECTRICAL PVC/NOT PLUMBING 5. IDENTIFY SPACE # AT PEDESTAL 6. A PERMIT IS NEEDED FOR ALL TRAILER REMODEL 7. CONDUIT COVERED BEFORE INSPECTION, TO BE MINIMUM 18" DEEP 8. NO TRAILER INSPECTION AT THIS TIME. |
|
11/14/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |