Permit: T07EL01798

Parcel: 133050700

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/11/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/28/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. DO NOT PARALLEL GROUNDING ELECTRODE CONDUCTOR
2. RECONNECT WATER BOND
3. SEAL ENTRANCES ABOVE CURRENT CARRING CONDUCTORS
4. LABEL ALL BREAKERS AS PER 408.4
5. A BOND BUSHING IS NEEDED ON SERVICE NIPPLE - 250.92
6. SEPARATE GROUNDING EQUIPMENT CONDUCTORS
7. PROTECT CABLES ENTERING BACK OF PANEL AND FILL UNUSED PORTION WITH A NON-COMBUSTIBLE PRODUCT
8. ANTI-OXIDE COMPOUND IS NEEDED ON ALL ALUMINUM CONDUCTORS
9. SECURE GROUNDING ELECTRODE CONDUCTOR TO WALL
10. NEED GAS BOND