Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/28/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. DO NOT PARALLEL GROUNDING ELECTRODE CONDUCTOR 2. RECONNECT WATER BOND 3. SEAL ENTRANCES ABOVE CURRENT CARRING CONDUCTORS 4. LABEL ALL BREAKERS AS PER 408.4 5. A BOND BUSHING IS NEEDED ON SERVICE NIPPLE - 250.92 6. SEPARATE GROUNDING EQUIPMENT CONDUCTORS 7. PROTECT CABLES ENTERING BACK OF PANEL AND FILL UNUSED PORTION WITH A NON-COMBUSTIBLE PRODUCT 8. ANTI-OXIDE COMPOUND IS NEEDED ON ALL ALUMINUM CONDUCTORS 9. SECURE GROUNDING ELECTRODE CONDUCTOR TO WALL 10. NEED GAS BOND |