Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SEPERATE GROUNDS AND INSTALL AS PER MANUFACTURERS INSTRUCTIONS 2) SHEET METAL SCREWS NOT ALLOWED 250.8 3) ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM CONDUCTORS 4) BOND SERVICE NIPPLE 25092 5) CIRCUIT DIRECTORY TO BE PER 408.4 |