Permit: T07EL01053

Parcel: 10612016A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07EL01053

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK TO CLEAR RECON
CALLED INTO JOANN 6/6/07
06/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DISCONNECT HAS OPEN HOLE ON TOP
2. DISCONNECT NOT SUPPORTED CORRECTLY
3. CORD HAS OPEN CONDUCTORS AT CORD CAP
4. NEED FUSE FOR 90 AMP RECEPTACLES
06/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ONE ON SITE, NO #8 MARKED
PRESUME ITS THE WHITE HOUSE - NO ONE THERE
CALLED 312-1571 NO ANSWER -- LEFT MESSAGE