Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07EL01053
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR RECON CALLED INTO JOANN 6/6/07 |
|
06/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DISCONNECT HAS OPEN HOLE ON TOP 2. DISCONNECT NOT SUPPORTED CORRECTLY 3. CORD HAS OPEN CONDUCTORS AT CORD CAP 4. NEED FUSE FOR 90 AMP RECEPTACLES |
|