Permit: T07EL00572

Parcel: 133380560

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND OFFSET NIPPLE PER NEC 250.92
2. BOND SERVICE RISER PER NEC 250.92
3. SIZE BONDING JUMPERS PER NEC 250.102
4. BOND 1" EMT AT SERVICE PANEL PER NEC 250.98
REDUCING WASHERS USED.
5. SPLIT BOLT CONNECTURES HAVE TOO MANY WIRES TERMINATED - NO MORE THAN 2 WIRES
6. LABEL PANEL PER NEC 408.4
7. VERIFY WATER & GAS BONDING
8. IS OLD METER ENCLOSURE RATED FOR 200 AMPS
9. SERVICE ENERGIZED PRIOR TO APPROVALS.