Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND OFFSET NIPPLE PER NEC 250.92 2. BOND SERVICE RISER PER NEC 250.92 3. SIZE BONDING JUMPERS PER NEC 250.102 4. BOND 1" EMT AT SERVICE PANEL PER NEC 250.98 REDUCING WASHERS USED. 5. SPLIT BOLT CONNECTURES HAVE TOO MANY WIRES TERMINATED - NO MORE THAN 2 WIRES 6. LABEL PANEL PER NEC 408.4 7. VERIFY WATER & GAS BONDING 8. IS OLD METER ENCLOSURE RATED FOR 200 AMPS 9. SERVICE ENERGIZED PRIOR TO APPROVALS. |