Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/04/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* OUTLET ON LEFT SIDE OF SUB-PANEL NOT ON APPROVED PLAN -- NOT GFI PROTECTED |
|
| 03/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDS & NEUTRALS TO BE ISOLATED AT SUB-PANEL UNDER PORCH. 3-WIRE FEEDER AT SUB-PANEL ONLY 2 WIRES INTO PEDESTAL?? 2. GROUND SYSTEM PROPERLY, INSTALL RACEWAY PER CODE SUPPORT PER CODE, CHASE NIPPLE NOT ALLOWED FOR TERMINATION INTO PEDESTAL. TERMINATIONS FOR LOADS NOT TO BE RUN THRU UTILITY COMPARTMENT. 3. 36" OF WORKING CLEARANCE IN FRONT OF SUB-PANEL COOLER J-BOX NOT SUPPORTED. |