Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07EL00530
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ALL FEEDERS AND GROUND RODS |
|
| 06/26/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS 1. INSTALLATION TO BE PER PLAN -- REVISE PLAN IF NEEDED 2. GROUNDING ELECTRODE SYSTEM WILL BE REQUIRED AT EACH PEDESTAL AND LAUNDRY LOCATION - NEC 250.32 |
|
| 06/20/2007 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
| 06/18/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* STILL NEED TO COMPLETE #2, 4, 9 FROM PREVIOUS INSPECTION DRIVE GROUND RODS FLUSH WHO WILL INSTALL SERVICE LATERAL CONDUCTORS? ?'S CHARLIE 349-5029 |
|
| 06/12/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SERVICE INSPECTION ONLY 1. PROVIDE PHYSICAL PROTECTION FOR SERVICE FROM VEHICULAR TRAFFIC SUCH AS BOLLARDS, ETC - NEC 110.27 2. IDENTIFY SERVICE DISCONNECTS AS SUCH - NEC 230.70B 3. PROVIDE GROUNDING ELECTRODE SYSTEM FOR SERVICES NEC 250.50 4. BOND ALL SERVICE RACEWAYS AND ENCLOSURES - NEC 250.92 5. TIGHTEN MAIN BONDING SCREWS IN DISCONNECTS - NEC 110, 250 6. TIGHTEN ALL CONDUCTOR CONNECTIONS NEC 110 7. TIGHTEN LOCKNUTS DISCONNECTS TO GUTTER - NEC 110 8. IDENTIFY NEUTRAL IN GUTTER - NEC 200 9. INSTALL FUSES, POWER WILL NOT BE APPROVED WITHOUT LOAD FOR SERVICE. |