Permit: T07EL00530

Parcel: 10706033A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07EL00530

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ALL FEEDERS AND GROUND RODS
06/26/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
1. INSTALLATION TO BE PER PLAN -- REVISE PLAN IF NEEDED
2. GROUNDING ELECTRODE SYSTEM WILL BE REQUIRED AT EACH PEDESTAL AND LAUNDRY LOCATION - NEC 250.32
06/20/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
06/18/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
STILL NEED TO COMPLETE #2, 4, 9 FROM PREVIOUS INSPECTION
DRIVE GROUND RODS FLUSH
WHO WILL INSTALL SERVICE LATERAL CONDUCTORS?

?'S CHARLIE 349-5029
06/12/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SERVICE INSPECTION ONLY
1. PROVIDE PHYSICAL PROTECTION FOR SERVICE FROM VEHICULAR TRAFFIC SUCH AS BOLLARDS, ETC - NEC 110.27
2. IDENTIFY SERVICE DISCONNECTS AS SUCH - NEC 230.70B
3. PROVIDE GROUNDING ELECTRODE SYSTEM FOR SERVICES
NEC 250.50
4. BOND ALL SERVICE RACEWAYS AND ENCLOSURES -
NEC 250.92
5. TIGHTEN MAIN BONDING SCREWS IN DISCONNECTS -
NEC 110, 250
6. TIGHTEN ALL CONDUCTOR CONNECTIONS NEC 110
7. TIGHTEN LOCKNUTS DISCONNECTS TO GUTTER - NEC 110
8. IDENTIFY NEUTRAL IN GUTTER - NEC 200
9. INSTALL FUSES, POWER WILL NOT BE APPROVED WITHOUT LOAD FOR SERVICE.