Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/14/2007 ELECTRIC - FINAL Cancelled IVRS - RI canceled
06/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/29/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CALL FOR FINAL ONCE ENERGIZED
05/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 250.32 OF NEC REQUIRES A GROUNDING CONDUCTOR TO BE INSTALLED WITH NEW FEEDERS.
2. BONDING JUMPER STILL NOT SIZED PROPERLY ON SERVICE RISER SHOULD BE 1/0 COPPER
3. WATER BOND TO BE SIZED 250.104 SHOULD BE 1/0 COPPER IF RUN TO 400 AMP SERVICE. IF INSTALLED TO PANEL SERVING HOUSE CAN BE SIZED PER 250.104(2)
04/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO PULL GROUND WIRE #4 TO SERVICE AT NEW BUILDING PER DRAWINGS E-1 & NEC 250.32
2. HAVE ENGINEER SPECIFY COPPER OR ALUMINUM FOR NEW FEEDERS.
3. DRAWING E-1 CALLS FOR 1/0 CU TO WTR BOND PER
NEC 250.104
4. DRAWING CALLS FOR GROUND RODS TO BE 8' APART
5. BONDING JUMPER ON SERVICE RISER TO BE SIZED PER
NEC 250.102 (C)
6. DRAWING E-1 CALLS FOR 2 GROUND RODS 8' APART AT 2ND BUILDING.
7. CHECK DEPTH OF 2 1/2" PVC MIN TO BE 18" TO TOP OF PIPE PER NEC 300.5