Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T07DV00693

Parcel: 110073890


Addresses:

2531 N COLUMBUS BL

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
02/21/2007 INSP - INITIAL CODE ENFORCMENT Approved SOUTH PORTION OF DWELLING CARPORT ENCLOSED AND BEING UTILIZED AS A BEDROOM. ELECTRICAL CIRCUITS ADDED. SOUTH WALL FLEXES APPROX 2-3 INCHES. HEAT PUMP INSTALLED ON THE ROOF WITHOUT PERMITS.
UNIT LACKs SMOKE DETECTORS
KITCHEN GFCI IS INOPERABLE AND IS TOO CLOSE TO WATER FAUCET. NORTH SIDE BEDROOM LACKS LIGHT SWITCH COVER. FRONT PORCH LIGHT LACKS GLOBE. MAIN SERVICE ELECTRICAL PANEL INSTALLED WITHOUT PERMITS. EXPOSED ROMEX EXITING TOP AND BOTTOM OF SERVICE BOX. PANEL IS NOT PROPERLY LABELED AND ADDRESSED. PANEL COVER DOES NOT FIT PROPERLY.
WATER HEATER LACKS VENT PIPE. LACKS TPRV PIPE. LACKS ENCLOSURE. WASHER LOCATED IN SOUTH BEDROOM CLOSET DRAINS TO THE REAR YARD AND IS NOT CONNECTED TO AN APPROVED SEWER SYSTEM. GAS SERVICE CONNECTION HAS TWO SERVICE LINES. ONE ENTERING THE STRUCTURE AND ONE INTO THE GROUND.
EVIDENCE OF ROACH INFESTATION. ROACHES EXITING ELECTRICAL PLUGS WHEN TESTING
WINDOWS INOPERABLE IN THE KITCHEN, LIVING ROOM, NORTH BEDROOM, CENTER AND SOUTH BEDROOM. PHOTOS TAKEN. RM