Permit: T07CM04809

Parcel: 133231470


Addresses:

7333 E ROSEWOOD ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04809

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/11/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/14/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE PHYSICAL PROTECTION FOR LFNC
2. PLEASE VERIFY LISTING FOR DOCK LEVELER
3. NEED TO SEE EQUIPMENT CONNECTIONS
4. NEED COPY OF GENERATOR REPORT
5. SIGNAGE PER 702.8 NEEDED
6. SIGNAGE PER 210.5(C) NEEDED
03/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ITEMS 1-7 OF PREVIOUS INSPECTION
03/27/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. ROOM #104: FINISH VDV CABLING
2. DISCONNECTING MEANS FOR WATER HEATER
3. ONLY ONE CONDUCTOR TO BOND CLAMP
4. CLEAN EXCESS DIRT & TRASH FROM FLOOR BOXES
5. NEED HANDLE TIES FOR MODULAR FURNITURE 605.7
6. PROTECT FLEXIBLE RACEWAY FROM PHYSICAL DAMAGE
7. USE APPROVED FITTINGS WITH LB'S - LIGHTING CONTROL SYSTEM
8. BOND ENCLOSURES - CONTROL CABINETS
9. FILL UNUSED OPENINGS IN GUTTER

FOR 3/28/08 COMPLETE #4 & #5 EXCEPT ROOM 111
03/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ROOM 116-118
03/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
LABEL DISCONNECTS
OK ROOMS 101-103, 110
03/20/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ROOMS 108, 109, 112-115, 119, 122, 126, 128-130
156, 158, 159
03/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. USE APPROVED MOUNTING HARDWARE FOR DEVICES
2. BOXES MORE THAN 1/4" OR 1/8" AROUND - 314.20, 314.21
03/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ROOMS 132-152, 160