Permit: T07CM04809

Parcel: 133231470


Addresses:

7333 E ROSEWOOD ST


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM04809

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/11/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/13/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HALLWAY #157
03/04/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HALLS 153-156, 112, 113, 114, 115, 158 & OFFICES
03/03/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE VDV CABLE TO CABLE TRAY PER 318
2. NEED SUPPORT WIRE FOR EXIT SIGN
3. MFG CLIPS MUST BE EFFECTIVE
4. SUPPORT M/C CABLE FOR RECOL SYS 604 & 330
5. SEAL UNUSED CONDUIT OPENINGS
6. SUPPORT VDV CABLE AS PER 725.6 AND NOT TO RACEWAY
7. BOND BUSHING FOR DISCONNECT 250.97
8. LABEL DISCONNECTS
9. MAINTAIN WORKING CLEARANCES AT DISCONNECTS
02/29/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection
02/22/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK CEILINGS RMS #111, 107, 106 AND 105
2) RECEIVED LETTER OF TORQUE
3) SAW GFI TEST REPORT FOR 2000 AMP MAIN
02/19/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING RMS. 104, 108, 109, 131, 116, 117, 118
02/13/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
ROOMS 132, 133, 137-148, 150, 151, 152 AND 102
02/12/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING - 250.8
2. CLEAN SURFACE UNDER LUG - 250.12
3. CABLES TO BE SECURED TO CABLE TRAY
UPON EXITING TRAY
4. SUPPORT VDV CABLING UP OFF OF GRID
725.6, 800.24, 300.11
02/05/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK WALLS & HARD LID ROOM 100
02/01/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
JUNCTION BOXES TO BE ACCESSIBLE
OK ROOMS 149, 160, 122 HARD LIDS
01/29/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/18/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK WALLS 110, 111, 122 AND PARTIAL 107