Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM04809
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
03/13/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HALLWAY #157 |
|
03/04/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HALLS 153-156, 112, 113, 114, 115, 158 & OFFICES |
|
03/03/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SECURE VDV CABLE TO CABLE TRAY PER 318 2. NEED SUPPORT WIRE FOR EXIT SIGN 3. MFG CLIPS MUST BE EFFECTIVE 4. SUPPORT M/C CABLE FOR RECOL SYS 604 & 330 5. SEAL UNUSED CONDUIT OPENINGS 6. SUPPORT VDV CABLE AS PER 725.6 AND NOT TO RACEWAY 7. BOND BUSHING FOR DISCONNECT 250.97 8. LABEL DISCONNECTS 9. MAINTAIN WORKING CLEARANCES AT DISCONNECTS |
|
02/29/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | ||
02/22/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CEILINGS RMS #111, 107, 106 AND 105 2) RECEIVED LETTER OF TORQUE 3) SAW GFI TEST REPORT FOR 2000 AMP MAIN |
|
02/19/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING RMS. 104, 108, 109, 131, 116, 117, 118 |
|
02/13/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE ROOMS 132, 133, 137-148, 150, 151, 152 AND 102 |
|
02/12/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SHEETMETAL THREAD SCREWS NOT ALLOWED FOR GROUNDING - 250.8 2. CLEAN SURFACE UNDER LUG - 250.12 3. CABLES TO BE SECURED TO CABLE TRAY UPON EXITING TRAY 4. SUPPORT VDV CABLING UP OFF OF GRID 725.6, 800.24, 300.11 |
|
02/05/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK WALLS & HARD LID ROOM 100 |
|
02/01/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* JUNCTION BOXES TO BE ACCESSIBLE OK ROOMS 149, 160, 122 HARD LIDS |
|
01/29/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/18/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK WALLS 110, 111, 122 AND PARTIAL 107 |