Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/08/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FINAL FOR BUILDING STILL NEED TO FINISH WORK FOR PROPANE DISPENSER AND TANK OR PULL SEPARATE PERMIT FOR THIS WORK. |
|
| 05/05/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED OVERCURRENT PROTECTION OF XFMR SECONDARIES PER NEC 240 - PLAN CALLS FOR 200AMP MAIN BREAKER 2. PROPANE TANK NOT FINISHED @ THIS TIME WAS TOLD THAT A SEPARATE PERMIT WAS BEING PULLED. |
|
| 04/27/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/06/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* CHECK WITH BUILDING INSPECTOR FOR TCO I HAVE NO ISSUES 1. INSTALL DISCONNECTING MEANS FOR SUMP PUMPS LOADING DOCKS 2. PROPANE TANK TO MEET REQUIREMENTS OF NEC 514 |
|
| 04/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OFFICES & BATHROOMS RECEPTACLES & SWITCHES ONLY OK 1. CONDUIT, JUNCTION BOXES FOR PROPANE TANK AND DISPENSER TO BE INSTALLED PER 514 OF THE NEC. |