Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK MACHINE AREA WEST OF 3RD GARAGE DOOR ONLY |
|
| 02/19/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* RECEIVED PAPERWORK FOR ENCLOSING ROMEX CABLES ABOVE DROP CEILINGS |
|
| 02/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS OFFICE AREA BASED ON LETTER FROM BOWDEN ENGINEERING ALLOWING USE OF NM CABLE IN OFFICE AREAS ONLY. STILL NEED TO RESOLVE ISSUE WITH NM CABLE ABOVE DROP CEILING SEE NEC 334.10 AND 334.12 |
|
| 01/29/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CALLED MATT FROM BOWDEN ENGINEERING HE STATES USE OF NM CABLE IS NOT ALLOWED. NEED TO PROVIDE INFORMATION ON ALLOWABLE WIRING METHODS. 2. ROMEX NOT ALLOWED TO BE USED ABOVE DROP CEILINGS IN OTHER THAN DWELLINGS 3. NO INSPECTION DONE |
|
| 09/10/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK U.G FOR FEEDERS TO PANELS & MCC & FUTURE FROM SES |