Permit: T07CM04729

Parcel: 141185300


Addresses:

9538 E OLD VAIL RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/17/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/05/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/27/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK MACHINE AREA WEST OF 3RD GARAGE DOOR ONLY
02/19/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
RECEIVED PAPERWORK FOR ENCLOSING ROMEX CABLES
ABOVE DROP CEILINGS
02/06/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS OFFICE AREA BASED ON LETTER FROM BOWDEN ENGINEERING ALLOWING USE OF NM CABLE IN OFFICE AREAS ONLY. STILL NEED TO RESOLVE ISSUE WITH NM CABLE ABOVE DROP CEILING SEE NEC 334.10 AND 334.12
01/29/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CALLED MATT FROM BOWDEN ENGINEERING HE STATES USE OF NM CABLE IS NOT ALLOWED. NEED TO PROVIDE INFORMATION ON ALLOWABLE WIRING METHODS.
2. ROMEX NOT ALLOWED TO BE USED ABOVE DROP CEILINGS IN OTHER THAN DWELLINGS
3. NO INSPECTION DONE
09/10/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK U.G FOR FEEDERS TO PANELS & MCC & FUTURE FROM SES