Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/23/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) G1 SHEARWALL TO GO BEHIND FIREPLACE NO DETAIL BETWEEN FLOORS. G1 ON BOTH SIDES ? 2) CHANGING SIZE OF WIRE ON CIRCUITS 12-14 3) CLEAN UP WIRES IN BOX, WIRE TOUCHING BUSS BAR 4) QUESTIONS ON H20 SERVICE H20 SOFTNER 5) GROUND ALL METAL BOXES 6) MAKE UP ALL ELECTRIC BOXES READY FOR DEVICE 7) RANGE CIRCUIT REQUIRES 4 WIRES 8) INSTALL STUCCO LATH 9) BLOCK 3 SIDES ALL MECH DUCTS 10) STRAP DRYER DUCT AT TOP PLATE 11) H20 SERVICE NOT SIGNED OFF SIZE NOT ON PLAN 3/4" WAS TO GO TO H20 HTR 1" COLD TO HOSE ? 12) SAFETY GLAS AT TUB |