Permit: T07CM04612

Parcel: 133369680

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T07CM04612

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
10/13/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
09/15/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) DO NOT ENERGIZE PANEL "B" UNTIL INSPECTED
2) NEED REVISED ELECTRICAL PLAN FOR ACCTUAL BLDGS INSTALLED
09/05/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. NEED TO POST BOND FOR POWER
2. BOND SERVICE RACEWAYS
3. INSTALL CONDUCTORS FROM CT CAN TO DISCONNECTS
4. MARK SERVICE DISCONNECTS
5. NOT A COMPLETE INSPECTION FINISH WORK AND RECALL
6. INSTALL UFER TO SERVICE
7. OK 1 1/2" PVC U.G FOR SIGN