Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 02/14/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PAINT ALL VTR STACK ON ROOF 2) ALL RECEPTACLE COVERS ON FLOOR MUST BE FLOOR TYPE 3) RECEPTACLE IN DINING ROOM SHOWING OPEN GROUND AND MASTER BEDROOM AND LIVING ROOM (4 PLACES) 4) ALL BEDROOM CONDUCTORS MUST BE ON A ARC FAULT TYPE BREAKER (SMOKE DETECTORS) 5) DEAD BOLT LOCK AT ENTRY DOOR NOT TO CODE, MUST BE ABLE TO OPEN FROM INSIDE WITHOUT A KEY 6) NEED SHEET METAL SCREWS IN DBL B-VENT AT WITH HEATER 7) SECURE ENCLOSURE WITH HEATER |