Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04338
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/04/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. RELOCATE FIXTURES TO BE SECURELY ATTACHED TO GRID 410.16 - 4 ON CORNERS OR 2 ON CENTER OK WALLS CK CEILING ON FINAL |
|
11/30/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE APPROVED STRAPS FOR M/C 2. SUPPORT M/C CABLES ON VERTICALS 3. PROTECT M/C CABLES INSIDE OF STUD CHANNELS - 330.17, 300.4 4. NEED BRACKET BOXES TO SUPPORT - NO SCREWS INSIDE OF BOXES 314.23 5. VDV CABLING TO BE AS PER 725.3 & 6, 800.3 & 6, 300.11 6. RELOCATE FIXTURES TO FACILITATE OPENING OF LENS COVERS 7. SUPPORT OR REMOVE NM CABLE ABOVE CEILING 8. BOX OVERFILLED 314.16 |