Permit: T07CM04289

Parcel: 11003081C

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM04289

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/26/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
TEST ON FUTURE VENT OK
09/24/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
YARD WATER OK TO COVER AFTER REMOVING ROCKS
SHADING W/CLEAN FILL
WATER PIPING OVERHEAD OK
INSTALL VAC BREAKERS ON ALL HBS OR REMOVE
PROVIDE TEST ON 4" VENT

- PROVIDE AN APPROVED PLAN REVISION FOR THE 3" PVC VENTS INSTALLED PER REDLINES.
- TEST ON PVC OK
- BACKWATER VALVE NOT SHOWN ON PLAN
08/19/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV INSPECTED UNDER ACTIVITY 00779
OVERHEAD COPPER OK
ISOLATE WHERE TOUCHING METAL
INSPECTION FOR EAST HALF OF BUILDING (3 EAST)
08/18/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. I SEE NO INSPECTION HISTORY FOR THE SECOND FLOOR
2. N/H TO BE SUPPORTED WITHIN 18" EACH SIDE OF A CONNECTION
3. VERTICAL PIPE TO BE SUPPORTED
4. NO PORTION OF ANY WORK MAY BE CONCEALED UNTIL IT HAS BEEN INSPECTED AND APPROVED
5. CONTINUED "NOT READY" WILL RESULT IN
REINSPECTION FEE