Permit: T07CM04289

Parcel: 11003081C

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T07CM04289

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
01/26/2009 ELECTRIC - TEMP POWER FOR TEST Approved
11/07/2008 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) STILL NEED TO BOND SPRINKLER AND BLDG STEEL
2) NEED LOAD REVISIONS FOR HOUSE PANEL #2 BLDG 3A
3) NEED 22 KAIC BREAKERS IN HOUSE PANEL PER PLANS
10/30/2008 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) NEED REVISION FOR CHANGES TO SERVICE
10/29/2008 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND GUTTER WITH PROPER SIZE JUMPER
2. BOND CT ENCLOSURE WITH PROPER SIZE JUMPER
3. SERVICE CONDUCTORS NOT SIZED PROPERLY FOR CALCULATED LOAD