Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2009 | MECHANICAL - FINAL | Approved | ||
| 06/25/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/22/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE GUARD RAIL ON ANY SERVICEABLE EQUIPMENT WITHIN 10' OF ROOF EDGE 2. PROVIDE SERVICE RECEPTACLE WITH GFCI WITHIN 25' OF EQUIPMENT 3. PROVIDE PERMANENT LADDER TO ACCESS UNIT OVER 30" HEIGHT (RFCU-1) 4. PROVIDE ACCESS TO UNIT AND RAILING AT RFCU-2 |
|
| 06/18/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ENGINEER REVIEWING BALANCE ISSUES |
|
| 06/17/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/16/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. DUCT DETECTOR REPORT OK 2. AIR BALANCE REPORT OK EXCEPT AHU-2 3. STILL NEED TO COMPLETE INSPECTION OF PENTHOUSE |
|
| 02/06/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/04/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ALL HYDRO-TESTING & PIPING OK 2. REMOVE CEILING TILES FIRST FLOOR PRIOR TO INSPECTION |