Permit: T07CM04093

Parcel: 14027064A


Addresses:

2525 E VALENCIA RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/26/2009 MECHANICAL - FINAL Approved
06/25/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
06/22/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE GUARD RAIL ON ANY SERVICEABLE EQUIPMENT WITHIN 10' OF ROOF EDGE
2. PROVIDE SERVICE RECEPTACLE WITH GFCI WITHIN 25' OF EQUIPMENT
3. PROVIDE PERMANENT LADDER TO ACCESS UNIT OVER 30" HEIGHT (RFCU-1)
4. PROVIDE ACCESS TO UNIT AND RAILING AT RFCU-2
06/18/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) ENGINEER REVIEWING BALANCE ISSUES
06/17/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
06/16/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. DUCT DETECTOR REPORT OK
2. AIR BALANCE REPORT OK EXCEPT AHU-2
3. STILL NEED TO COMPLETE INSPECTION OF PENTHOUSE
02/06/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/04/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1. ALL HYDRO-TESTING & PIPING OK
2. REMOVE CEILING TILES
FIRST FLOOR PRIOR TO INSPECTION