Permit: T07CM04093

Parcel: 14027064A


Addresses:

2525 E VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
01/22/2009 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
1) NO BOND REQUIRED PER J. SANDERS
2) CONTRACTOR RESPONSIBLE FOR ONLY AUTHORIZED PERSONS TO HAVE ACCESS TO ELECTRIC EQUPMENT
01/02/2009 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
1) A BOND WILL BE NEEDED FOR TEMP POWER
2) BONDING JUMPERS LINE SIDE TO BE PER 250.102 & 250.66
3) ILLUMINATION NEEDED IN ELECTRIC ROOM 110.26 (D)
4) NEED LOCK OUT/TAG OUT BOOK ON SITE FOR PROCEDURES
5) NEED MANUFACTURERS BOOK TO VERIFY IF CABLE BRACING IS NEEDED
6) RECEIVED LETTERS FOR TORQUE AND GFI TESTING OF MAIN