Permit: T07CM04093

Parcel: 14027064A


Addresses:

2525 E VALENCIA RD

Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Date Description Inspector Results Comments
06/22/2009 BUILDING - PROGRESS Approved IVRS - Inspection :*
04/16/2009 BUILDING - PROGRESS Partial Approval IVRS - Inspection :*
1. WESTERN TECH. FINAL EARTH WORK, CONCRETE, MASONRY, POST INSTALLED ANCHORS, WELDING,
STEEL CONSTRUCTION, HIGH STRENGTH BOLTS -- ALL FOUND COMPLIANT
04/10/2009 BUILDING - PROGRESS Partial Approval IVRS - Inspection :*
GUARD RAIL NOT REQ. IF NEW DETAIL FOLLOWED
AT 3RD FLOOR CATWALK
04/08/2009 BUILDING - PROGRESS Partial Approval IVRS - Inspection :*
REVIEWED PLANS AND ACCESSIBILITY
04/02/2009 BUILDING - PROGRESS Partial Approval IVRS - Inspection :*
1. ADA USED STATE BLDG.
2. NEED GUARD RAIL AT PENTHOUSE
SOUTH SIDE CATWALK
03/27/2009 BUILDING - PROGRESS Partial Approval IVRS - Inspection :*
WHICH WAS USED FOR CODE ANALYZING ANSI 2003 OR ADA
06/20/2008 BUILDING - PROGRESS Partial Approval IVRS - Inspection :*
1. 2ND FLOOR DECK 3 TO 4 A TO F INSTALLING WW CHAIRS
SPECIAL INSPECTED - OK TO POUR
2. NEED TO SEE CORRECTED NON-COMPLIANCE REPORTS FROM WESTERN TECH