Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04039
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/11/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK DRINKING FOUNTAIN ROUGH 1, 2, 3 RD NE SIDE |
|
08/14/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT MC PER NEC, TO STRUCTURE, NOT OTHER PIPING 2. INSULATE CABLE WHERE TOUCHING COPPER WATER LINES |
|
08/01/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK RESTROOM #119 & #120 & DRESSING ROOMS OK DRINKING FOUNTAINS SOUTHEAST 1ST, 2ND, 3RD FLOOR |
|
07/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK GREEN ROOM ROUGH |
|
07/17/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLUG UNUSED KO IN 4 GANG SWITCH BOX AND SUPPORT CONDUITS PROPERLY (EAST DOOR) 2. OK WEST ENTRANCE |
|
05/27/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK #139 & #140 ROUGH ELECTRIC & CEILING |
|
05/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CONDUITS FOR ELEV. LIFT #106 OK RESTROOM #123 |
|
04/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH FOR EDF IN HALLWAY 1ST FLOOR #237 |
|
03/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH FOR EDF BASEMENT #124 |
|
03/21/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |