Permit: T07CM03771

Parcel: 12216115A


Addresses:

2351 N ALVERNON WY


Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Permit Number - T07CM03771

Inspection Description - PLUMBING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2008 PLUMBING - PROGRESS Approved IVRS - Inspection :*
INSTALL ATMOSPHERIC VACUUM BREAKER
ON EXTERIOR HOSE BIBB

- A TRAP ARM MAY NOT CHANGE SIZE
- A TRAP AND TRAP ARM TO BE THE SAME SIZE
- TRAP MAY BE ONLY ONE PIPE SIZE LARGER THAN THE TAILPIECE TO WHICH IT IS CONNECTED.
01/09/2008 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*
1. AT HANDSINK: FEMALE ABS THREADS MAY NOT BE INSTALLED IN AN UNACCESSIBLE LOCATION
2. WATER HEATER WILL REQUIRE AN EXPANSION TANK
FOR FINAL
3. ALL EXISTING INDIRECT WASTE PIPING TO HAVE SLOPE AND BE MADE SANITARY (1" AIR GAP)
4. ALL NEW I.W PIPING TO BE OF APPROVED MATERIAL TYPE INSTALLED WITH SLOPE TO A 1" AIR GAP
5. ONLY ONE SLIP NUT ON THE OUTLET SIDE OF A TRAP AT NEW SINK AND REMOVE CLEANOUT COVER FOR SINK FOR INSPECTION.