Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON ROOF 1. DISCONNECTS TO BE IDENTIFIED WITH LABEL SUITABLE FOR ENVIRONMENT 2. WEST ICE CONDENSOR OVERFUSED 3. ALL EQUIPMENT TO BE MARKED PROPERLY AS IN PANEL DIRECTORY - AS PER NEC 408.4 INSIDE 1. IDENTIFY SERVICE DISCONNECT AND PANEL IT DISCONNECTS 2. EMERGENCY LIGHTING TO BE PER PLAN PARTIAL INSPECTION - STILL NEED CEILING INSPECTION HAVE TILES OPEN IN AREAS NEEDED |