Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/08/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* MAINTAIN WORKING AND DEDICATED CLEARANCES PER 110.26 |
|
| 01/04/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 12/28/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 12/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 5 RECPETACLES AT ? WALL PER PHONE CONVERSATION (MC) |
|
| 12/20/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 12/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 12/11/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLANS SHOW 200 AMP MAIN FOR PANEL "R" 2. SEAL OPENING PANEL "R" - NEC 300 3. BONDING CONDUCTORS TO BE #2 CU - NEC 250.66 4. BOND NEUTRAL TO SERVICE DISCONNECT ENCLOSURE - NEC 250.24 C 5. INSTALL FUSES PARTIAL INSPECTION |