Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/17/2009 | MECHANICAL - FINAL | Partial Approval | 1. COUNTERTOP SURFACE IS NON COMBUSTIBLE COMPOSIT. 2. DISTANCE TO LVOUP FROM FRONT OF COOKING SURFACE WITHIN 4' |
|
| 09/16/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/14/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PER 507.1 IMC-ALL SURFACES WITHIN 18" OF COOKING SURFACE MUST BE NON COMBUSTIBLE. SUCH AS SHEETMETAL OR CERAMIC TILE 2) PER 507.12 O,C-THE INSIDE EDGE OF HOOD SHALL OVER HANG COOKING APPLIANCE BY A MIN. OF 6" ON ALL OPEN SIDES. THE VERTICAL DISTANCE BETWEEN THE FRONT LOWER LIP AND THE COOKING SURFACE SHALL NOT EXCEED 4' 3) PROVIDE COOKING APPLIANCE INSTALLATION INSTRUCTIONS |
|
| 08/27/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |