Permit: T07CM03770

Parcel: 11713069E

Inspection Status: Approved

Inspection History: MECHANICAL - HOOD SYSTEMS

Date Description Inspector Results Comments
10/01/2009 MECHANICAL - HOOD SYSTEMS Approved
08/28/2009 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTOR TEST REPORTS OK, 1 COPY SUBMITTED WITH INSPECTION REPORT
2) HEAT SENSOR INTERLOCK AND MVA/EXHAUST INTERLOCK OK
3) STILL NEED HINGE KIT.
4) NO LIFE SAFETY ISSUES OBSERVED
5) SEE BLDG INSPECTOR FOR TEMP C OF O
08/27/2009 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
1) SEAL ALL JOINTS AND SEAMS ON HOOD AND WALL FLASHING
2) SMOKE CONTAINMENT TEST ON HOOD OK
3) HEAT SENSOR ON HOOD FAILED
4) UNABLE TO TEST E.F./M.V.A. INTER LOCK
08/05/2009 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
1) 1ST LAYER WRAP COMPLETE, OK FOR SECOND LAYER FIRE WRAP
08/04/2009 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
1) SMOKE TEST OK
2) OK FOR 1ST LAYER
08/03/2009 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
1) OK 1ST LAYER 2ND LAYER OF DROP THUR CURB ON KITCHEN EXHAUST DUCT
07/30/2009 MECHANICAL - HOOD SYSTEMS Not ready for Inspection IVRS - Inspection :*
TURN OUT AREA OK TO ROCK LID