Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOOD SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2009 | MECHANICAL - HOOD SYSTEMS | Approved | ||
| 08/28/2009 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* 1) DUCT SMOKE DETECTOR TEST REPORTS OK, 1 COPY SUBMITTED WITH INSPECTION REPORT 2) HEAT SENSOR INTERLOCK AND MVA/EXHAUST INTERLOCK OK 3) STILL NEED HINGE KIT. 4) NO LIFE SAFETY ISSUES OBSERVED 5) SEE BLDG INSPECTOR FOR TEMP C OF O |
|
| 08/27/2009 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* 1) SEAL ALL JOINTS AND SEAMS ON HOOD AND WALL FLASHING 2) SMOKE CONTAINMENT TEST ON HOOD OK 3) HEAT SENSOR ON HOOD FAILED 4) UNABLE TO TEST E.F./M.V.A. INTER LOCK |
|
| 08/05/2009 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* 1) 1ST LAYER WRAP COMPLETE, OK FOR SECOND LAYER FIRE WRAP |
|
| 08/04/2009 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* 1) SMOKE TEST OK 2) OK FOR 1ST LAYER |
|
| 08/03/2009 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* 1) OK 1ST LAYER 2ND LAYER OF DROP THUR CURB ON KITCHEN EXHAUST DUCT |
|
| 07/30/2009 | MECHANICAL - HOOD SYSTEMS | Not ready for Inspection | IVRS - Inspection :* TURN OUT AREA OK TO ROCK LID |