Permit: T07CM03770

Parcel: 11713069E

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
08/07/2009 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
02/26/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
2" FORCE MAIN ON EAST SIDE OF BUILDING TEST OK AND TRACER WIRE OK
12/12/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
SOUTH SIDE OF BUILDING SUMP PUMP FOR AREA DRAIN TEST
TRACER WIRE OK
12/11/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. 2" PVC FROM SUMP PUMP FROM AREA DRAIN TEST OK
2. C1.2 HAS HIGHLIGHT FOR SITE SEWER BEDDING TRACER WIRE - SDR35 OK TO BE TESTED AT LATER DATE
12/10/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
11/21/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST ON INTERCEPTOR OK
11/19/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
HIGHLIGHT ON PAGE P1.2
11/17/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
CANCELED
10/30/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PER HIGHLIGHT ON P1.2
10/23/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
AREA DRAIN PIPING COMPLETE
10/21/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
COMPLETE AREA DRAWING BEFORE CALLING IN FOR INSPECTION
10/17/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PER HIGHLIGHT ON PAGE P1.2
10/15/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
AREA DRAIN ON SOUTHEAST END OF BUILDING
10/13/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PARTIAL PRE-HIGHLIGHT ON PAGE P.1.2
09/29/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PERIMETER DRAIN ALONG SOUTHWEST CORNER OK TO COVER
PERIMETER DRAIN ALONG "K" LINE OK TO COVER
09/24/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
09/19/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
P.11A & P.1.1 PER HIGHLIGHT
TEST OK
09/10/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
08/21/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
HIGHLIGHT ON P.1.1 AND P1.1 FOR DRAIN PIPING TEST OK
08/14/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ROUGH SOIL PER HIGHLIGHT ON P1.0
08/07/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) HIGHLIGHT TEST OK ON FLOOR DRAWING ON PAGE P1.0
08/06/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) IS PIPING PER PLAN ? PROVIDE NEW TEST
2) PIPING TO FLOOR SINK REMOVE MUD ? DRY FILL
08/04/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
AREA DRAIN PER HIGHLIGHT ON PAGE P1.0
07/16/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. PER HIGHLIGHT ON PAGE P1.0 FLOOR SINK PIPING TEST JUST PAST STORAGE/P206/NORTHWALL
2. AREA DRAIN ON WEST SIDE OF BUILDING PER
HIGHLIGHT P1.0
07/08/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. 4" PVC BLDG. PERIMETER DRAIN, EXTENDED FROM 05/28/08
TO NORTHERNMOST POINT OF THE BUILDING - OK TO COVER
2. I DID NOT SEE ANY PERIMETER DRAINAGE PIPING INSTALLED ON THE WEST SIDE OF THE BLDG.
06/25/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. CONTRACTOR WILL WRAP ALL PIPING AT P-208 LOWER LEVEL PARKING
2. OK TO POUR THIS AREA ONLY
06/24/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. SUNDT HAS NOT SECURED A PERMIT FOR WATER TO THE TRAILER. A PRESSURE VACUUM BREAKER IS NOT THE CORRECT BACKFLOW DEVICE AND ALL HOSE BIBS ARE TO HAVE AVB's IMMEDIATELY
2. YOU ARE STILL COVERING WITHOUT PERMISSION
3. ALL FIXTURE TRAPS, INTERCEPTORS, ETC. REQUIRE VENTS
06/23/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. PLEASE POST YOUR ADDRESS - SEE ACCOMPANYING DISPLAY REQUIREMENTS
2. THE LETTER ACCEPTING 1% MUST BE ON ENGINEER'S LETTERHEAD WITH STAMP
3. I DID NOT GIVE PERMISSION TO COVER ROUGH/SOIL AT THIS AREA
4. PIPING IS NOT COMPLETE IN THIS AREA
5. I CAN DO PARTIALS BUT TRY AND GIVE ME A COMPLETE SECTION AT A TIME
6. NEED TO SEE VENT AT LIFT STATION
06/20/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. YOU HAVE AN ADDRESSING PROBLEM
300 S FIRE CENTRAL PL DOES NOT EXIST
495 W CUSHING NEEDS TO BE POSTED AND REFLECTED ON YOUR PERMIT

2. CORRECT BACKPITCHED SECTIONS.
ALL PIPING TO HAVE 2% GRADE UNLESS NOTED OTHERWISE

3. N/H BANDS ARE LISTED FOR CAST IRON. USE MISSION BAND AT N/H X PL

4. PROVIDE ENGINEERING FOR ACCEPTANCE AT 1%
05/28/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
4" PVC SOUTH END OF BUILDING 10' GOING WEST AND FROM SOUTH END TO NORTH END 120' (4" DRAIN TILE TO SUMP PIT)
PAGE A3.2