Permit: T07CM03770

Parcel: 11713069E

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
10/14/2009 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
10/09/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/28/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/18/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/17/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/11/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK LOWER LEVELS LIGHTING
2) OK BATHROOM ? LIGHTING
EXTERIOR:
1) LABEL GATE DISCONNECTS
2) LOOSE LOCK NUTS
3) NO TREE WELL LIGHTS
4) WEST SIDE GATE CONTROLS
INTERIOR:
1) FINISH CLIMATE WIRING
2) FINISH SECURITY WIRING
3) NEED SURFACE MOUNTED FIXTURES
09/03/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK PVC, RIGID AND POLE BASES AS MARKED
09/02/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/01/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK ROOM 115 AND 134
2) OK PVC AND RIGID CONDUITS AS MARKED
08/31/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/28/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK EM LIGHTS ALL
2) OK PVC CONDUIT AS MARKED
ROOM 116:
1) BOXES MORE THAN 1/4" 314.20
ROOM 117:
1) LIGHTS FLASHING
ROOM 115:
1) DUAL SWITCHING
08/26/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/25/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/24/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK ROOMS FOR FINAL 101-103,105,119 A & B, P100 AND P200
2) OK ABOVE CEILING 100B,200B AND 400B
3) OK 2 GROUND RODS SERVICE "G" + #6 SDBC
4) OK WATER HEATER ROOMS EXCEPT LIGHTING
FAN ROOMS:
1) FINISH CLIMATEC WIRING
2) LABEL DISCONNECTS
GARAGE LOWER LEVELS:
1) FINISH DOOR MOTORS
2) STILL NEED DISCONNECTING MEANS 410.73 (G)
2ND FLOOR KITCHEN AND DINING ROOM:
1) FINISH VDV CABELING
HOSE TOWER:
1) NEED TO FINISH
BELL TOWER:
1) FINISH LIGHTING AT BELL
APPARATUS BAY:
1) FINISH MAKE UP CONTROL CABINETS
2) LABEL EQUIPMENT
3) FINISH LIGHTING
4) FINISH WEST ROOMS
GENERATOR:
1) VERIFY 25 OHMS OR LESS GROUNDING
2) NEED LABELING 700.8
EMERGENCY KILL TEST:
LIGHTS NOT WORKING-1ST FLOOR:
1ST FLOOR
1) BREAK ROOM, BATHROOMS, WEST END, 133, 151, APPARATUS BAY HALL 105 AND FITNESS ROOM
LIGHTS NOT WORKING 2ND FLOOR:
1) BREAK ROOM, STAIRWELL 200 AND 100E
NOTE:
1) WAITING ON ANSWERS FOR SURFACE LIGHTING
08/21/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
08/20/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/19/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/18/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/17/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/14/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/13/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
1) REMOVE CEILING 204-A COVERED WITHOUT INSPECTION
08/12/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK ROOMS FOR FINAL 118,121-126 A & B, 133, 153-157, 276-281
ROOF:
1) LABEL EQUIPMENT
2) TIGHTEN LOOSE FITTINGS
3) SUPPORT SEAL TITE
4) PROTECT SEAL TITE FROM SHARP METAL EDGES
5) BOND BUSHINGS AT CONCENTRIC
6) FINISH ACCESS COUNTER CONTROLS
08/11/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/10/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK ABOVE CEILING ROOM 202, 207-OK PVC CONDUIT AS MARKED
2) SUPPORT BOX ELEVATOR LOBBY LOWER LEVEL 1
GENERATOR:
1) FINISH GROUNDING ELECTRODE SYSTEM
2) CANNOT STACK LUGS
3) ANCHOR TO SLAB
4) WILL NEED A COPY OF TEST REPORT
08/07/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/06/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/05/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/04/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
08/03/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/31/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/30/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
07/29/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
07/28/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/27/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/24/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/23/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/22/2009 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
07/21/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/20/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/17/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/16/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/15/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/14/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/13/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/10/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/09/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/08/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/07/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/06/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/02/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/01/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/30/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/29/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
06/29/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/26/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
06/25/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/24/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/23/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
06/23/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/22/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/19/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/18/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/17/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/16/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/15/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/11/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/09/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/08/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/04/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
06/02/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
05/29/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
05/27/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
05/21/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
05/18/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
05/15/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
05/14/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
05/12/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
05/07/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
05/06/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
05/01/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
04/01/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*