Permit: T07CM03770

Parcel: 11713069E

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
09/28/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
09/18/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/17/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/16/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/11/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/01/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/31/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
ROOM 115:
1) LIGHTS NOT PER PLANS
COMM ROOM 126 B:
1) DISCONNECTING MEANS FOR A/C ?
2) CIRCUIT DIRECTORY PANEL "UP"
3) ARC SHIELDS 314.20
ELECTRIC ROOM 126 A:
1) CIRCUIT DIRECTORIES 408.4
COMM ROOM 256 B:
1) DISCONNECTING MEANS A/C ?
08/26/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/25/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/24/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/21/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/20/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/19/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/18/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/17/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/14/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FINISH LIGHTING CONTROLS-CONFERENCE
2) PLEASE VERIFY LISTING AND LABELING WINDOW SHARE MOTORS-CONFERENCE
3) SUPPORT COAX 810.24 AND 820.14
4) NEED TO POWER CHECK DORMS
5) OK ABOVE CEILING 200 D, 209, 211, 225, 231, 241, 107 & 108
6) OK ROOMS FOR FINAL 286 + A, 252-256 A & B, 244-250, 257-263, 267, 268 & 200 D
ROOF:
1) FINISH TIGHTENING FITTINGS
2) LABEL EQUIPMENT
3) FILL UNUSED BOX OPENING
08/13/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/12/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/11/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/10/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/07/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/06/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/03/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/31/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/29/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/28/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/27/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/24/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/23/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/22/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
07/21/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/20/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/17/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/14/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/13/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/10/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/09/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
P201:
1) CORRECTLY SUPPORT CONDUIT TO STRUCTURE
2) MISSING LB COVER
3) FINISH BOX MAKE UP
4) LABEL EQUIPMENT
P203A:
1) SUPPORT CONDUIT
2) TIGHTEN LOOSE FITTINGS
P205:
1) LABEL EQUIPMENT
2) FINISH BOX MAKE UP
3) DO NOT STACK GROUND LUGS AND ONLY ONE CONDUCTOR PER LUG
4) SEAL TIGHT INSIDE OF AIR HANDLERS IN ENVIORMENTAL AIR
5) BOND DISCONNECT ENCLOSURE
07/08/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/07/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/06/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/02/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/01/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/30/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/29/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/26/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/25/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/24/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/23/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/23/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/22/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/19/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/17/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/16/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/09/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/08/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/02/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/18/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HARD LIDS 289-290
05/14/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/07/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/01/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/23/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FIRST FLOOR BATHROOMS AND LOCKERS OK
2) SOUTH WALL OFFICE AND MIDDLE OFFICES OK
3) EAST SIDE SOUTH OFFICES AND MIDDLE OFFICES OK WALLS ONLY
4) ATRIUM LIGHTING CONDUIT ADD CONDUIT TO REDUCE DEGREES IN RUN OK
04/01/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
NO MORE THAN 360 DEG. IN CONDUIT RUNS
OK ATRIUM CEILING
02/17/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK WALLS, EAST OF ELEC. ROOM 1ST FLOOR
2. CALL IN WALL INSPECTIONS UNDER INTERMEDIATE (02035)
02/12/2009 ELECTRIC - ABOVE CEILING Cancelled IVRS - RI canceled
01/22/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK ELEC. ROOM 1ST FLOOR WALLS