Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/18/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/17/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/16/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/11/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/01/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/31/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* ROOM 115: 1) LIGHTS NOT PER PLANS COMM ROOM 126 B: 1) DISCONNECTING MEANS FOR A/C ? 2) CIRCUIT DIRECTORY PANEL "UP" 3) ARC SHIELDS 314.20 ELECTRIC ROOM 126 A: 1) CIRCUIT DIRECTORIES 408.4 COMM ROOM 256 B: 1) DISCONNECTING MEANS A/C ? |
|
| 08/26/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/25/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/24/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/21/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/20/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/19/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/18/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/17/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/14/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH LIGHTING CONTROLS-CONFERENCE 2) PLEASE VERIFY LISTING AND LABELING WINDOW SHARE MOTORS-CONFERENCE 3) SUPPORT COAX 810.24 AND 820.14 4) NEED TO POWER CHECK DORMS 5) OK ABOVE CEILING 200 D, 209, 211, 225, 231, 241, 107 & 108 6) OK ROOMS FOR FINAL 286 + A, 252-256 A & B, 244-250, 257-263, 267, 268 & 200 D ROOF: 1) FINISH TIGHTENING FITTINGS 2) LABEL EQUIPMENT 3) FILL UNUSED BOX OPENING |
|
| 08/13/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/12/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/11/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/10/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/07/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/06/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/03/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/31/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/29/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/28/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/27/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/24/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/23/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/22/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 07/21/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/20/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/17/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/14/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/13/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/10/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/09/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* P201: 1) CORRECTLY SUPPORT CONDUIT TO STRUCTURE 2) MISSING LB COVER 3) FINISH BOX MAKE UP 4) LABEL EQUIPMENT P203A: 1) SUPPORT CONDUIT 2) TIGHTEN LOOSE FITTINGS P205: 1) LABEL EQUIPMENT 2) FINISH BOX MAKE UP 3) DO NOT STACK GROUND LUGS AND ONLY ONE CONDUCTOR PER LUG 4) SEAL TIGHT INSIDE OF AIR HANDLERS IN ENVIORMENTAL AIR 5) BOND DISCONNECT ENCLOSURE |
|
| 07/08/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/07/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/06/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/02/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/01/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/30/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/29/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/26/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/25/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/24/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/23/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/23/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/22/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/19/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/17/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/16/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/09/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/08/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/02/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/18/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HARD LIDS 289-290 |
|
| 05/14/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/07/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/01/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 04/23/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FIRST FLOOR BATHROOMS AND LOCKERS OK 2) SOUTH WALL OFFICE AND MIDDLE OFFICES OK 3) EAST SIDE SOUTH OFFICES AND MIDDLE OFFICES OK WALLS ONLY 4) ATRIUM LIGHTING CONDUIT ADD CONDUIT TO REDUCE DEGREES IN RUN OK |
|
| 04/01/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* NO MORE THAN 360 DEG. IN CONDUIT RUNS OK ATRIUM CEILING |
|
| 02/17/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK WALLS, EAST OF ELEC. ROOM 1ST FLOOR 2. CALL IN WALL INSPECTIONS UNDER INTERMEDIATE (02035) |
|
| 02/12/2009 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
| 01/22/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK ELEC. ROOM 1ST FLOOR WALLS |