Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/19/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/18/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FILL UNUSED CONDUIT OPENINGS ABOVE PANELS 2) VERIFY B-1 AND E FIXTURES FOR SURFACE MOUNT-GYP BOARD FLANGED 3) BOXES MORE THAN 1/4" FROM BOX TO SURFACE 4) FINISH BATHROOMS 5) OK LID ROOM 204A 6) OK ABOVE CEILING 200E, 205 & 206 7) OK DORM ROOMS FOR FINAL 8) OK KITCHEN ISLAND WIRING |
|
| 08/13/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/11/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 1 MC CONDUIT REPAIRS BACK OF APPARATUS BAY 2) OK PVC CONDUIT REPAIR STREET LIGHTING ON GRANADA |
|
| 08/04/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/03/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK POLE BASES AS MARKED 2) OK EXTERIOR LOBBY HOOD 3) OK JUNCTION BOXES ABOVE CEILING 2 |
|
| 07/31/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK REDO FOR PVC REMOTE ANNUNCIATOR PANEL 2) OK PVC PER GATE ISLAND 3) OK ABOVE CEILING 286 A AND 266 EXCEPT AT PULL BOXES 4) OK WALLS 100 D 5) POLE BASES NOT READY-DO NOT POUR |
|
| 07/30/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/29/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/28/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK POWER FOR PROJECTOR 121 2) OK PVC POLE TO POLE AS MARKED |
|
| 07/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/24/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND FLOOR: 1) SUPPORT FIXTURE 1 PER 4' OF FIXTURE-KITCHEN 2) FINISH VDV-RM 286 3) FINISH POWER FOR PROJECTOR-ROOM 121 4) OK ELECTRIC ABOVE CEILING ROOM 121 AND 286 AS NOTED 5) OK ELECTRIC ABOVE CEILING ROOM 252-255 |
|
| 07/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/21/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PVC IN WALLS FOR LOW VOLTAGE AT MOUNUMENTS IN FRONT 1ST FLOOR: 1) WHAT IS WITH PROJECTOR AND SCREEN 2ND FLOOR: 1) FINISH VDV CABELING 2) FINISH MAKE UP |
|
| 07/20/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH VDV CABELING 2) NEED MECHANICAL CLAMP FOR LIGHTING CONDUCTORS 3) FINISH POWER POLES 4) ATTACH FIXTURES TO GRID 5) BOX OVER FILLED 6) OK ABOVE CEILING 243-250, 257-263 7) OK WALLS AND LID P100A |
|
| 07/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PVC CONDUIT AT MONUMENT AS MARKED 2) LIGHTS LOWER LEVELS: PROVIDE DISCONNECTING MEANS AT FIXTURE 410.63 (G) AND FILL UNUSED OPENINGS IN FIXTURES |
|
| 07/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/14/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/13/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS 204 (B) 2) OK PVC CONDUIT AS MARKED 3) MAINTAIN CLEARANCES AT VAV IN KITCHEN 206 |
|
| 07/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/08/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CELL 269-277,282-284 2) OK HARD LID AND WALLS STAIRWELL 100A 1ST FLOOR |
|
| 07/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH ROOMS 2) FINISH ABOVE CEILINGS 3) OK THE LV PVC RUN INTO LOWER LEVEL 1 |
|
| 07/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ELECTRIC LIGHTS AND CONDUIT ROOM 121-FINISH VDV CABELING 2) OK HARD LIDS AND WALLS STAIRWELL 200A-2ND FLOOR 3) OK HARD LID ROOM 116 4) OK CANS SOFFIT 242 5) OK PVC CONDUIT FOR LV LIGHTING 6) OK RIGID ACROSS FOOTING |
|
| 07/02/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILING ROOM 2) OK HARD LID ROOM #223,227,235,239 & 200G 3) OK 6 WALKWAY LIGHTS AND CONDUIT AS MARKED SUBJECT AFTER HOLIDAY MEMORIAL: 1) GROUND ROD FOR LIGHTING DAMAGED AND BENT CANNOT USE |
|
| 07/01/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/30/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/29/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 750 KUA XFMR: POND PER 250.122-BOLT TO PAD 2) NEED INSTRCUTIONS FOR SECURING UPS TO PAD 3) NEED ILLUMINATION AT PANELS 110.26 4) LABEL COVERS OF PANELS AND SWITCH BOARD PER 210.5 FOR SYSTEMS 5) DERATE IN GUTTTER ? 366 6) A BOND WILL BE NEEDED FOR TEMP POWER FOR TEST 7) OK ELECTRIC ABOVE CEILING ROOMS 123-125 AND 127 8) OK EQUIPMENT WITH GREEN LABELS 9) OK TO MAIN LUGS ONLY 1ST AND 2ND FLOOR 126 AND 256A |
|
| 06/26/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/25/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK REDO PVC & RIGID ENTRY BOLLARDS OK 234, 233A, 221 |
|
| 06/24/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CAN SOFFIT RM.208 OK PVC CONDUIT AS MARKED |
|
| 06/23/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CORRIDOR 268.201 HARD LIDS OK FLEX CONDUITS RM. 118 OK ELECTRIC ABOVE CEILING 129-133 AFTER CORRECTIONS OK HARD LID RM. 266, 242A |
|
| 06/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUPPORT VDV CABLING 725.24 AND 300.11 |
|
| 06/19/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK LIDS STAIRWELL 200C ALL LEVELS 2) OK WALLS STAIRWELL 200A 3) OK WALLS AND LIDS 235,237,229 & 226 4) OK WALLS AND NORTH SOFFIT 208 |
|
| 06/18/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) OK 4-4" PVC CONTINUATION EAST TO WEST TO VAULT 70' |
|
| 06/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD LIDS 212, 214, 216, 218, 220, 224, 213, 215, 217, 228, 230, 232, 236, 238, 240, CORRIDOR 264 IN FRONT OF ELEC. RM. OK ABOVE CEILING 139-151 AFTER CORRECTIONS 1. SUPPORT VDV CABLING 725.24, 300.11 -- SPEAKERS 2. ATTACH TO CABLE TRAY UPON EXITING 3. SECURELY ATTACH FIXTURES TO GRID 410.16 4. FINISH INSTALLING CORD FOR LIGHTS PER MFG. INSTRUCTIONS |
|
| 06/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 3 LIGHTS IN CONCRETE IN FRONT OF GAZEBO OK WALLS 200H, 22, 219 1. CORDS NOT ALLOWED ABOVE CEILING - INSTALL AS PER MANUFACTURES INSTRUCTIONS 2. SUPPORT VDV CABLING 725.24, 800.24, 300.11 |
|
| 06/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/11/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE ROCK & INSULATION ROOMS 228, 230, 232 TO INSPECT *DO NOT ONE SIDE WITHOUT INSPECTORS APPROVAL 2. REMOVE TEMP WIRING BEFORE ROCKING LID OK WALLS ONLY 213, 215, 217, 226, 236, 238, 240, 203 OK LID CORRIDOR 264 |
|
| 06/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND FLOOR CORRIDOR LID ELECTRIC ROOM NORTH |
|
| 06/08/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD LID 109 OK ROOMS 212, 214, 216, 218, 220, 222, 224 - WALLS AND LIDS |
|
| 06/02/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/29/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK POLE BASES AS MARKED OK WALLS ROOM 101, 102 1. JUNCTION BOXES TO BE ACCESSIBLE |
|
| 05/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/21/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/15/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* ANSWERED CODE QUESTIONS OK PVC FOR SITE LIGHTS AS MARKED |
|
| 05/14/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/12/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROOMS 286, 286A, 289, 290 |
|
| 05/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 7 PVC CONDUITS TO LIGHTS AND GAZEBO OK ROOM 112, 118 AND 119 HARD LIDS JUNCTION BOXES TO BE ACCESSIBLE |
|
| 05/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/01/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HALL 278, ROOM 254-255A, 200D, 285, 286A, 243 OPEN TO BELOW COLUMNS OK CORRIDOR CEILINGS 122 TO COLUMN LINE "G" 135, 152, 137 1. UNCOVER STAIRWELLS FOR INSPECTIONS *FINISH ROOMS TO GET ROOM INSPECTIONS ALSO, DO NOT COVER WITHOUT INSPECTIONS. *ELECTRIC ROOM TO MEET REQUIREMENTS OF 110.26 |
|
| 04/01/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |