Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07CM03770

Parcel: 11713069E

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
09/28/2009 ELECTRIC - UFER Approved IVRS - Inspection :*
08/24/2009 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
08/06/2009 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1) OK LID 256A
2) OK TO TEST AH.4, FC-9, AH-3, BFC-2
3) OPEN LIGHTS AS DIRECTED IN DORM AREA
4) BOXES MORE THAN 1/4" 314.20
5) NEED SUPPORT WIRE EXIT LIGHTS
MAIN ELECTRIC ROOM:
1) SECURE DRIP PAN OVER UPS
2) PROVIDE INFORMATION ON SECURING UPS PER SYSMIC REQUIREMENTS
3) OK NEW GROUNDED AND CADWELD FOR LIGHTING
4) OK ROOMS 269-275 EXCEPT POWER OK, ALSO DORM ROOMS
07/15/2009 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
GENERATOR:
1) OK CONDUITS UNDER GENERATOR SLAB
2) OK GROUND ROD-VERIFY 25 ? OR LESS
3) OK LIGHTING CONDUCTOR AT GENERATOR
4) OK OUTDOOR CONDUITS AS MARKED
07/16/2008 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
INSTALL GROUND RODS, UFER COVERED PRIOR TO INSPECTION