Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2009 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 08/24/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* | |
| 08/06/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) OK LID 256A 2) OK TO TEST AH.4, FC-9, AH-3, BFC-2 3) OPEN LIGHTS AS DIRECTED IN DORM AREA 4) BOXES MORE THAN 1/4" 314.20 5) NEED SUPPORT WIRE EXIT LIGHTS MAIN ELECTRIC ROOM: 1) SECURE DRIP PAN OVER UPS 2) PROVIDE INFORMATION ON SECURING UPS PER SYSMIC REQUIREMENTS 3) OK NEW GROUNDED AND CADWELD FOR LIGHTING 4) OK ROOMS 269-275 EXCEPT POWER OK, ALSO DORM ROOMS |
|
| 07/15/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* GENERATOR: 1) OK CONDUITS UNDER GENERATOR SLAB 2) OK GROUND ROD-VERIFY 25 ? OR LESS 3) OK LIGHTING CONDUCTOR AT GENERATOR 4) OK OUTDOOR CONDUITS AS MARKED |
|
| 07/16/2008 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* INSTALL GROUND RODS, UFER COVERED PRIOR TO INSPECTION |