Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* AIR COMPRESSOR REMOVED WILL NEED TO PULL SEPARATE PERMIT FOR INSTALLING ANY NEW EQUIPMENT |
|
| 07/01/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CONNECT EQUIPMENT GROUNDS TO POLES @ HAND OPENING LIGHT POLES 2. NEED BONDING BUSHINGS ON 277/480V CIRCUITS WHERE RACEWAYS ENTER CONCENTRIC KNOCKOUTS DISCONNECTS AND PANELS 3. HAVE ENGINEER VERIFY CONDUCTOR SIZE TO MOTOR LOADS IN SHOP AREA PER NEC 430 |