Permit: T07CM03741

Parcel: 14111365A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/02/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
AIR COMPRESSOR REMOVED WILL NEED TO PULL SEPARATE PERMIT FOR INSTALLING ANY NEW EQUIPMENT
07/01/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CONNECT EQUIPMENT GROUNDS TO POLES @ HAND OPENING LIGHT POLES
2. NEED BONDING BUSHINGS ON 277/480V CIRCUITS WHERE RACEWAYS ENTER CONCENTRIC KNOCKOUTS DISCONNECTS AND PANELS
3. HAVE ENGINEER VERIFY CONDUCTOR SIZE TO MOTOR LOADS IN SHOP AREA PER NEC 430