Permit: T07CM03503

Parcel: 12218450B

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
10/03/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
10/02/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
TRAP PRIMER NOT PROPERLY CONNECTED AT DRAIN
PIPING NOT PER PLAN - REDLINES NOT COMPLETE, UNAPPROVED REVISION IS NOT ACCURATE.
09/28/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
HAVE REDLINES DRAWN IN ON APPROVED PLAN PRIOR TO PRE-SLAB INSPECTION.
RECALL FOR INSP. BEFORE CONCRETE
09/27/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
- TEST ON DWV OK
- GT NOT INSTALLED PER PLAN. REDLINE CHANGES OF GW AND GT ORIENTATION
- INSTALL CLEANOUTS REQUIRED. 135 DEG. MAX CHANGE OF DIRECTION
- MAKE CONNECTION TO GT
- CORRECT SLOPE ON 2" GW
- RECALL FOR INSP PRIOR TO COVERING
09/21/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
SOIL PIPE OK, 3" NOT PENETRATING FOOTING
RECALL FOR CONTINUATION OF GW AND FOR FS AND FD INSTALLATION
09/20/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) NOT INSTALLED PER PLAN-NO RED LINES ON SITE
2) WILL REQUIRE 3" DISCHARGE ON GREASE TRAP