Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/18/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. WIRING NOT PER PLAN, SHOWS SEPARATE CKT'S TO UNITS 2. HAVE UNDERSIZED EQUIPMENT GROUNDS TO J-BOX 3. SEAL INTERIOR OF RACEWAY INTO WALK-IN 4. FAN COIL WILL NEED A DISCONNECT AND MAX 15 AMP OVERCURRENT PROTECTION 5. HAVE OVERFILLED J-BOXES 6. HAVE OVERFILLED WIRE NUTS 7. WIRING NOT COMPLETE/NOT PER PLAN PARTIAL INSPECTION - CEILING TILES NOT TO BE INSTALLED |