Permit: T07CM03503

Parcel: 12218450B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/26/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/18/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. WIRING NOT PER PLAN, SHOWS SEPARATE CKT'S TO UNITS
2. HAVE UNDERSIZED EQUIPMENT GROUNDS TO J-BOX
3. SEAL INTERIOR OF RACEWAY INTO WALK-IN
4. FAN COIL WILL NEED A DISCONNECT AND MAX 15 AMP OVERCURRENT PROTECTION
5. HAVE OVERFILLED J-BOXES
6. HAVE OVERFILLED WIRE NUTS
7. WIRING NOT COMPLETE/NOT PER PLAN

PARTIAL INSPECTION - CEILING TILES NOT TO BE INSTALLED