Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/18/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* SEE BLDG. INSPECTOR FOR C.O 2 DUCT SMOKE DETECTORS TESTED OK |
|
| 03/17/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE AUDIBLE AND VISUAL ALARM ON DUCT SMOKE DETECTORS |
|
| 03/10/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE DUCT SMOKE DETECTORS ON NEW EQUIPMENT IN EXCESS OF 2000 CFM |
|
| 02/05/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* GRIDLINES A THRU D AND 1 THRU 8 OK TO FINAL ALSO, CORRIDOR 205C AND NEW ELECTRICAL TEST AREA 223-T AND 224-T OK TO FINAL |
|
| 01/23/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CONNECTIONS TO HOODS OK COLUMN LINE D EAST OK ON FINAL |
|
| 12/18/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* WEST END FINAL OK SEE BUILDING INSPECTOR FOR TEMP C OF O THIS AREA ONLY |
|
| 11/30/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* GAS CARD LEFT AT SITE BOND MUST BE POSTED WITHIN 5 DAYS |