Permit: T07CM03323

Parcel: 140420940

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/18/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
SEE BLDG. INSPECTOR FOR C.O
2 DUCT SMOKE DETECTORS TESTED OK
03/17/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE AUDIBLE AND VISUAL ALARM ON DUCT SMOKE DETECTORS
03/10/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE DUCT SMOKE DETECTORS ON NEW EQUIPMENT IN EXCESS OF 2000 CFM
02/05/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
GRIDLINES A THRU D AND 1 THRU 8 OK TO FINAL
ALSO, CORRIDOR 205C AND NEW ELECTRICAL TEST AREA
223-T AND 224-T OK TO FINAL
01/23/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
CONNECTIONS TO HOODS OK
COLUMN LINE D EAST OK ON FINAL
12/18/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
WEST END FINAL OK
SEE BUILDING INSPECTOR FOR TEMP C OF O THIS AREA ONLY
11/30/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
GAS CARD LEFT AT SITE
BOND MUST BE POSTED WITHIN 5 DAYS