Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07CM03308

Parcel: 141113700

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/14/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/07/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. SUPPORT EXHAUST DUCTS
2. PROVIDE SUN SHIELDS OVER CANVAS CONNECTORS
3. SUPPORT WATER LINES TO EVAP. COOLERS
4. FOIL TAPE NOT APPROVED SEALANT OUTDOORS
5. REMOVE ALL TAPE & USE APPROVED DUCT SEALER
6. PROVIDE 22X22 GRILLS AS PER PLANS OR REVISE PLANS
7. PLANS REQUIRED FULL SIZE DRAINS TO LANDSCAPE FROM EVAP. COOLERS