Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/07/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. SUPPORT EXHAUST DUCTS 2. PROVIDE SUN SHIELDS OVER CANVAS CONNECTORS 3. SUPPORT WATER LINES TO EVAP. COOLERS 4. FOIL TAPE NOT APPROVED SEALANT OUTDOORS 5. REMOVE ALL TAPE & USE APPROVED DUCT SEALER 6. PROVIDE 22X22 GRILLS AS PER PLANS OR REVISE PLANS 7. PLANS REQUIRED FULL SIZE DRAINS TO LANDSCAPE FROM EVAP. COOLERS |