Permit: T07CM03308

Parcel: 141113700

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/14/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/07/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GFI RECEPT. KITCHEN INDICATES NOT WIRED PROPERLY WHEN TESTED
2. WALL MOUNTED HEATERS NOT PER PLAN
3. 30 AMP. CIRCUITS REQUIRE #10 GROUND
4. INSTANT HOTS NOT PER PLAN RATING ON 2 UNITS
INDICATES 208V WHEN SERVICE IS 240V
PLAN CALLS FOR 115V UNITS
5. INSTALL PER PLAN OR REVISE PLANS