Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 09/09/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) PROVIDE LETTER FROM ENGINEER FOR PANEL "P" TO BE MLO. ALSO OK TO HAVE PARALLEL 3/0 FROM DISCONNECT TO PANEL |
|
| 09/05/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. UNDERGROUND FROM XFMR TO SES NEVER INSPECTED NEEDS TO BE EXPOSED. 2. SECONDARY CONDUCTORS FROM XFMR TO SES TO BE INSTALLED 3. NEED TO POST BOND FOR POWER 4. INSTALL FUSES 5. EXPOSE CONNECTION FROM BOND JUMPER OF BUILDING STEEL TO GEC |