Permit: T07CM03308

Parcel: 141113700

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
11/14/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
09/09/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) PROVIDE LETTER FROM ENGINEER FOR PANEL "P" TO BE MLO. ALSO OK TO HAVE PARALLEL 3/0 FROM DISCONNECT TO PANEL
09/05/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. UNDERGROUND FROM XFMR TO SES NEVER INSPECTED
NEEDS TO BE EXPOSED.
2. SECONDARY CONDUCTORS FROM XFMR TO SES TO BE INSTALLED
3. NEED TO POST BOND FOR POWER
4. INSTALL FUSES
5. EXPOSE CONNECTION FROM BOND JUMPER OF BUILDING STEEL TO GEC