Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CLEAN EXCESS PAINT & FOREIGN MATERIAL FROM DEVICES AND TERMINALS --- 110.12 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS -- 314.20 3. WHERE IS APPROVED PLANS OR LETTER? |